PCB Mounted Zero Phase Sequence ZCT Current Sensor Transformers 2021-09-14T07:38:17+08:00

PCB Mounted Zero Phase Sequence Current Transformer

Customized Products are available upon request

General introduction and definition of Zero phase sequence current transformer

1. The basic function of current transformers

The current transformers can convert primary currents with larger values to secondary currents with lower values through a certain transformation ratio, which are used for protection and measurement purposes. For example, a current transformer with a transformation ratio of 400/5 can convert the actual 400A current to 5A current.

2. Working principle of zero phase sequence current transformer

The basic principle of zero-sequence current protection is based on Kirchhoff’s current law: the algebraic sum of the complex current flowing into any node in the circuit is equal to zero. When the line and electrical equipment are normal, the vector sum of each phase current is equal to zero. Therefore, the secondary winding of the zero sequence current transformer has no signal output, and the actuator does not operate. When the ground fault occurs, the vector sum of each phase current is not zero. The fault current causes magnetic flux in the ring core of the zero-sequence current transformer. The induced voltage on the secondary side of the zero-sequence current transformer causes the actuator to move and drive Trip device to switch the power supply network to achieve the purpose of ground fault protection.

3. The function of zero phase current sensor

When an electric shock or leakage fault occurs in the circuit, the protection acts and the power supply is cut off.

4. Conditions of use for zero phase sequence current transformers

A current transformer can be installed on each of the three-phase lines, or three-phase conductors can be passed through a zero-sequence current transformer together, or a zero-sequence current transformer can be installed on the neutral line N to use it to detect three phases. Vector sum of current.

For the specific application of zero-sequence current protection, a current transformer (CT) can be installed on each of the three-phase lines, or three-phase conductors can be passed through a zero-sequence CT together, or a zero-sequence CT can be installed on the neutral line N. These CTs are used to detect the vector sum of three-phase current, that is, the zero-sequence current Io, IA+IB+IC=IO, when the three-phase load connected to the line is fully balanced (no ground fault, and the leakage current of the line and electrical equipment is not considered ), IO=0; when the three-phase load connected to the line is unbalanced, then IO=IN, and the zero-sequence current at this time is the unbalanced current IN; when a ground fault occurs in a phase, a single-phase ground must be generated The fault current Id, the zero sequence current detected at this time IO=IN+Id, is the vector sum of the three-phase unbalanced current and the single-phase ground current.

PCB mounted Zero phase sequence current transformer

Zero Phase Current Sensor Applications

– Residual current circuit breaker (RCCB)
– Earth leakage circuit breaker (ELCB)
– Ground fault circuit interrupter (GFCI)
– Appliance leakage circuit breaker interrupter (ALCI)
– ZCT for energy storage system (ZCT’s)

Zero Phase Sequence Current Transformer Features

– Minimum output voltage tolerance
– Close to zero load shift
– Minimum noise output at 360 degree hair-pin test.
– Excellent thermal properties in minimal variation

Customized products are available

Product Main Materials and Electrical Diaphram

Zero Phase Sequence ZCT Current Sensor Transformers Main Materials
Core  80% Ni amorphous or nanocrystaline core
Core case PBT 1320 (UL file NO E221630)
Windings 2-UEN φ0.08mm (UL file NO E164502)
Shield metal shield
Epoxy Resin Epoxy resin 9001A/B (UL file No E105888)
Outer Case PBT 1320 (UL file NO E221630)
Lead wire PVC insulated wire 1007 #26AWG (UL file NO E186019)

Zero Phase Current transformer ZCT Electrical Property & Dimension

Model No Rated current Output voltage (V0/mV) Test Condition Over leakage characteristics Temperature Characteristics

(35ºC-80ºC)

Dimensions (mm)
A B C D
KXRKCT106-100

30

8-14

lin=30mA,RL=1kΩ¸

-10%~0%

10%Max

6.8 17.3 7

KXRKC106-100

30

6.3-7.3

lin=22.5mA RL=1kΩ¸

-10%~0%

10%Max

6.8 18.2 7.2

KXRKCT105-100

20

7.5-10.5

lin=11.25mA RL=1kΩ¸

-10%~0%

10%Max

5.5 15.4 6

KXRKCT109-100

30

17-21

lin=22.5mA RL=1kΩ¸

-10%~0%

10%Max

9.3 20.9 7.2

KXRKCT105-100

30

17-21

lin=22.5mA RL=1kΩ¸

-10%~0%

10%Max

5 17 9.5

KXRKCT106-100

30

25-30.5

lin=20mA RL=1kΩ¸

-10%~0%

10%Max

6 18.6 10

KXRKCT107-100

20

4.8-5.1

lin=20mA RL=1kΩ¸

-10%~0%

10%Max

6.8 17.5 7.8

KXRKCT108-100

30

3.2-4

lin=25mA RL=330Ω¸

-10%~0%

10%Max

8.1 18 6.5

KXRKCT107-100

40

6.3-7.3

lin=22.5mA RL=1kΩ¸

-10%~0%

10%Max

7.1 17 19.1

KXRKCT109-100

50

17-22

lin=11mA,RL=2kΩ¸

-10%~0%

10%Max

9 23 8.3

KXRKCT112-100

50

20-24

lin=20mA RL=1kΩ¸

-10%~0%

10%Max

12 26.7 11

KXRKCT106-100

40

25-30

lin=25mA RL=1kΩ¸

-10%~0%

10%Max

5.8 19.3 7.8

KXRKCT109-100

30

7.5-12

lin=30mA,RL=1kΩ¸

-10%~0%

10%Max

9.3 20.9 7.5

KXRKCT107-100

40

6.4-7.5

lin=20mA RL=1kΩ¸

-10%~0%

10%Max

6.8 17.4 6.5

KXRKCT105-100

30

3.6-3.8

lin=500mA,RL=150Ω¸

-10%~0%

10%Max

5.5 15.4 5.3

KXRKCT109-100

50

12-13

lin=25mA RL=330Ω¸

-10%~0%

10%Max

9 22 8.3

KXRKCT109-100

20

3.5-4.5

lin=20mA,RL=370Ω¸

-10%~0%

10%Max

6.4

KXRKCT109-100

30

15-18

lin=500mA,RL=150Ω¸

-10%~0%

10%Max

17

KXRKCT119-100

30

13.2-17.8

lin=11mA,RL=360Ω¸

-10%~0%

10%Max

19 5 7.5

KXRKCT107-100

20

4.8-5.1

lin=20mA RL=1kΩ¸

-10%~0%

10%Max

6.8 17.5 7.8

NOTE:

Above are just some of our models. More zero phase sequence current transformer models to come!  

Customized products are available upon request

Other Current Transformer For You to Choose, By Simply Clicking On Below Product Pictures

lead wire zero phase sequence current transformer
One stop solution for your current transformer needs
Busbar DC immunity current transformer

Ask us for price and solutions today for your zero phase sequence current transformer zct needs !

Your inquiry will be replied within 24 hours, and we respect your privacy.